VFD

VFDs are found on AC Fans, Pumps, and other motor driven entities and are used to control the motor speed.

Variations

  • VFD

A variation on VFDs exists called a VSD, which is a DC only VFD. That entity type is not explored in this shape.


Composition

Core

Nil

Switch

Nil

A VFD does not have any components that are required to be modelled.

Relationships

Core

Nil

Switch

  1. A VFD must be (immediately) part of a Pump or Fan (or any of their subclasses)
    path: brick:isPartOf
    pathRequirements: [
    pathDistance: 1
    ]
    validationType: propertiesOfValues
    properties: [
    or (
    classOrSubClassOf: brick:Pump,
    classOrSubClassOf: brick:Fan
    )
    ]

Points

All

An entity of this type is expected to have a selection of points from this provided list. Any points assigned that are not on this list will throw a warning.

Point NamePoint Class
Active Energy Deliveredswitch:Active_Energy_Delivered_Sensor
Active PowerActive_Power_Sensor
Cold Plate Temperatureswitch:Cold_Plate_Temperature_Sensor
CurrentCurrent_Sensor
DC Ripple Voltageswitch:DC_Ripple_Voltage_Sensor
DC VoltageDC_Bus_Voltage_Sensor
Demand Active Power
Demand Apparent Power
Electrical Energy Usedswitch:Electrical_Energy_Usage_Sensor
Enable CommandEnable_Command
Enable StatusEnable_Status
Fault Modeswitch:Fault_Mode_Status
Fault StatusFault_Status
FrequencyFrequency_Sensor
Heatsink TemperatureHeat_Sink_Temperature_Sensor
Mode
Motor Temperatureswitch:Motor_Temperature_Sensor
Override Modeswitch:Override_Mode_Status
Override StatusOverriden_Status
Power Supply Status
Reverse Commandswitch:Reverse_Direction_Command
Rotation Direction Statusswitch:Rotation_Direction_Status
Run CommandOn_Off_Command
Run StatusOn_Off_Status
SpeedSpeed_Sensor
Speed Commandswitch:Speed_Command
TorqueTorque_Sensor
Total After Hours Mode Runtime
Total RuntimeRun_Time_Sensor
Total Start Count
VoltageVoltage_Sensor

Minimum Set

The minimum selection of points Switch Automation expects to see on an entity of this type.